13.14.090 Grease interceptor/trap standards.
A. Minimum Requirements. The minimum requirements for interceptor
construction, materials and other features shall be those required by the
Uniform Plumbing Code (UPC), latest edition and any modifications, revisions or
amendments made by the city. A minimum size of grease interceptor of seven
hundred gallons with at least two compartments (effective
liquid volume of
five hundred gallons in the first compartment and two hundred gallons in the
second compartment) is recommended by the city. If the wastewater discharge flow
rate of a business is such that a larger system is recommended based on UPC
(Uniform Plumbing Code) criteria, then the larger sized system should be
installed.
B. Special Requirements. The size and type of grease interceptor
shall be subject to the approval of the city’s building inspection
department. The grease interceptor shall be installed in a line separate from
other sanitary plumbing facilities. In general, all grease interceptors shall be
designed for exterior installation, of capacity sufficient to service those
grease generating fixtures connected thereto. Wastes other than those requiring
separation shall not be discharged into the grease interceptor. Grease traps
shall be designed, located and constructed in a manner that will permit easy
access and maintained by the operator and inspected by the city. (Ord. 1485-95
§ 2(part), 1995).